Acyclic Extended Diagnostics /General Fault Codes (cont'd)
LCD
Meaning (cont' d )
display
The IDENT number used in
communications, and number
S: 32
selected by the Ident Number
Selector do not correspond.
Factory calibration for the
internal temperature sensor
S:33
has been lost.
Factory calibration for the
S:34
device has been lost.
Factory calibration for the
S:35
device has been lost.
Unable to start microwave
S:36
module.
Measurement hardware
S:37
problem.
Microwave module hardware
failure: unable to calculate
S:38
distance measurement.
Factory calibration for the radar
S:43
receiver has been lost.
Acyclic Data
SITRANS LR260 supports up to four simultaneous connections by a Class 2 Master
(C2 connection). It supports one connection by a Class 1 Master (C1 connection).
In order for a Class 1 Master to read parameters from an instrument, it needs to know the
slot and absolute index of the parameter.
The parameters are all listed in SIMATIC PDM under Help. If you do not have SIMATIC
PDM you can download the EDD and reference the HTML help file directly.
Page 132
SITRANS LR260 (PROFIBUS PA) – OPERATING INSTRUCTIONS
Corrective Action
Ensure value of the Ident
number selector is correct for
the network configuration. If it is
correct, the device needs to be
re-parameterized by the PLC.
Repair required: contact your
local Siemens representative.
Repair required: contact your
local Siemens representative.
Repair required: contact your
local Siemens representative.
Cycle power. If error persists,
contact your local Siemens
representative.
Cycle power. If error persists,
contact your local Siemens
representative.
Cycle power. If fault persists,
contact your local Siemens
representative: repair required.
Repair required: contact your
local Siemens representative.
Byte
Bit
(cont' d )
4
5
(continued on next page)
A5E32337685
0
1
2
3
4
5
6
3