6.3.2
Digital outputs
Changing the function of a digital output
Table 6-4
0
r0052.00
r0052.01
r0052.02
r0052.03
r0052.04
r0052.05
r0052.06
r0052.07
The complete list of binector outputs is provided in the List Manual.
Application example: Changing the function of a digital output
Advanced settings
You can invert the signal of the digital output using parameter p0748.
For more information, please see the parameter list and the function block diagrams 2230 f of
the List Manual.
SINAMICS G120C converter
Operating Instructions, 09/2017, FW V4.7 SP9, A5E34263257B AF
Frequently used binector outputs (BO) of the inverter
Deactivating digital output
1 signal: Ready for switching on
1 signal: Ready for operation
1 signal: Operation enabled
1 signal: Fault active
The inverter inverts signal
r0052.03 if it is interconnected to
a digital output.
0 signal: OFF2 active
0 signal: OFF3 active
1 signal: Closing lockout active
1 signal: Alarm active
Overview of the manuals (Page 459)
Overview of the manuals (Page 459)
6.3 Adapt the default setting of the terminal strip
To change the function of a digital output, you must in‐
terconnect the digital output with a binector output of
your choice.
Binector outputs are marked with "BO" in the parameter
list of the List Manual.
Interconnecting signals in the converter
(Page 447)
r0052.08
r0052.09
r0052.10
r0052.11
r0052.13
r0052.14
r0052.15
r0053.00
r0053.02
r0053.06
To output inverter fault messages via digital output DO 1, you
must interconnect DO1 with these fault messages.
Set p0731 = 52.3
Advanced commissioning
0 signal: Deviation, setpoint/actual
speed
1 signal: Control requested
1 signal: Maximum speed (p1082)
reached
0 signal: I, M, P limit reached
0 signal: Alarm overtemperature motor
1 signal: Motor CW rotation
0 signal: Alarm inverter overload
1 signal: DC braking active
1 signal: Speed > minimum speed
(p1080)
1 signal: Speed ≥ setpoint speed (r1119)
165