6.15.2.4
Setting the filter for fail-safe digital inputs
Requirement
You are online with STARTER or Startdrive online.
Procedure with STARTER
Proceed as follows to set the input filter and the simultaneity monitoring of the fail-safe digital
input:
1. Select the "Extended settings" button.
2. Set the debounce time for the F-DI input filter.
3. Set the discrepancy time for the simultaneity monitoring.
4. Close the screen form.
You have set the input filter and the simultaneity monitoring of the fail-safe digital input.
Procedure with Startdrive
Proceed as follows to set the input filter and the simultaneity monitoring of the fail-safe digital
input:
1. Navigate to the filter settings.
2. Set the debounce time for the F-DI input filter.
3. Set the discrepancy time for the simultaneity monitoring.
You have set the input filter and the simultaneity monitoring of the fail-safe digital input.
SINAMICS G120C converter
Operating Instructions, 09/2017, FW V4.7 SP9, A5E34263257B AF
Advanced commissioning
6.15 Safe Torque Off (STO) safety function
223