Main Contactor - Vacon NX series User Manual

Active front end unit (afe) air cooled
Hide thumbs Also See for NX series:
Table of Contents

Advertisement

Active Front End (AFE)
4.13

Main contactor

If a main contactor is to be used, the types shown in Table 25 are recommended. If a contactor from
another manufacturer is used, it must be equivalent to the types shown. Further information on the
contactors shown is available from the manufacturer.
Type
FI9
A210-30-11-80
Type
FI9
A185-30-11-80
Type
AF400-30-11-70
FI10
Type
AF300-30-11-70
FI10
Type
FI13
AF1650-30-11-70
Type
FI13
AF1350-30-11-70
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
Table 25. Recommended main contactor types
FI9 Contactor / 500 V
Contactor, 350 A/690 V, AC3 110 KW/400 V, 230 VAC-Coil
FI9 Contactor / 690 V
Contactor, 275 A/690 V, AC3 132 KW/690V, 230 VAC-Coil
FI10 Contactor / 500 V
Contactor, 600 A/500 V, AC3 200KW/400V, 100...250 V AC/DC coil
FI10 Contactor / 690 V
Contactor, 500 A/690 V, AC3 250 KW/690 V, 100...250 V AC/DC coil
FI13 Contactor / 500 V
Contactor, 1650 A/500 V, AC3 560 KW/400 V, 100...250 V AC/DC coil
FI13 Contactor / 690 V
Contactor, 1350 A/690 V, AC3 --- KW/400 V, 100...250 V AC/DC coil