Step
Action / Condition
1
Press the 'Acknowledge' button
or
press <Acknowledge> on the Person
Machine Interface
2
Reading the status information:
'Fire Brigade requested'
l
'Fire Brigade in' 'mm:ss'
l
'Call Fire Brigade !' if:
l
Remote transmission switched off
Remote transmission blocked or
defective
No remote transmission available
3
Press the 'Intervent.txt.' button if displayed
4
Read off fire location on display
5
Optional: press <Alarm device> on the
Person Machine Interface (password
required)
6
Go to the fire location
7
Decide: MAJOR INCIDENT or minor incident
Condition
Fire brigade has been called
'Fire Brigade in' 'mm:ss'
Countdown is running
'Call Fire Brigade !'
No automatic transmission to
the fire brigade
Building Technologies
Fire Safety
MAJOR INCIDENT
Save people
Guide the fire brigade to the fire
location
Fight the fire
Trigger the manual call point
immediately
or
Press 'All alarm delays off'
Call the fire brigade on the phone!
A password is required for resetting.
It may be necessary to air the room before 'Reset' is possible.
You can temporarily switch off elements that cannot be reset.
Consequence / Status
⇨ With 'AVC' countdown t2 for examination of the
cause of 'ALARM' starts
⇨ 'ALARM' is transmitted to fire brigade
⇨ 'ALARM' is transmitted to fire brigade in mm:ss
⇨ Remaining time is shown as Countdown
⇨ Fire brigade must be called by phone!
⇨ No automatic transmission to fire brigade
⇨ Intervention text is displayed
⇨ Deactivates the acoustic alarm devices
Minor incident
Try to prevent fire brigade
deployment
Press 'Reset' (password required)
Press 'Reset' (password required)
Operation
5
ALARM procedure
103