Ending 'Detector test' for all automatic 'Detectors' in an 'Area'
1. Repeat steps 1 - 7 of the instruction: Test all automatic 'Detectors' of a 'Area.
a The 'Select command' dialog window opens.
2. Select the 'Non-MCP zones det.test END' command.
a The 'DETECTOR TEST' LED goes out.
a The command execution display confirms successful execution of the
command by displaying
a The 'Detector test' is at an end.

Carrying out the walk test

Proceed as with 'Detector test' and select the 'Walk test' function.
l

Carrying out an installation test

As in the 'Installation test' all functions of the complete fire detection system
including the 'Fire control' and alarming are tested, you must take appropriate
actions.
The 'Installation test' can be carried out at 'Area' or ↑ 'Section' levels.
WARNING
During the installation test, the alarming and ↑ fire control are activated!
Personal injury resulting from extinguishing activation
The fire brigade is called up unnecessarily.
Set the 'Fire controls' to 'Control test' in advance.
Inform the fire brigade in advance.
Before the 'Installation test' you can set 'Fire controls' to 'Control test'.
No activation of manual call point zones
Manual call point zones are not activated in the 'Installation test'. The 'Installation
test' is not available for manual call point zones.
.
A6V10380629_en--_a
2015-09-10