5.7.4
Building Technologies
Fire Safety
Testing the ↑ site
Proceed as with 'Detector test' and select the 'Installation test' function.
l

Control test

The 'Control test' checks the function of configured controls.
During the 'Control test', the controls function in the same way as during normal
operation; however, the hardware is not actuated.
The ↑ effects of the controls, e.g., the actuation of digital outputs and the sounders
or the execution of commands is ensured, but the respective hardware receives no
signal and is thus not activated.
All controls can be set to 'Control test'.
Testing a control
w You are logged onto at least 'Access level' 2.2.
w You are in 'Main menu'.
1. Select the 'Functions' menu item.
a The 'Functions' menu is displayed.
2. Select the 'Test' menu item.
a The 'Functions 'Test'' dialog window opens.
3. Press 'Open' to open the 'Element category' filter.
Operation
5
Testing
137
A6V10380629_en--_a
2015-09-10