Status of the hibernation mode
Number
r2273
r2397
r2399
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
Name
Display of the setpoint/actual value deviation of the technology controller
Actual hibernation mode output speed
Actual boost speed before the pulses are inhibited or the actual start speed after restart.
Hibernation mode status word
00 Hibernation mode enabled (p2398 <> 0)
01 Hibernation mode active
02 Hibernation mode delay time active
03 Hibernation mode boost active
04 Hibernation mode motor switched off
05 Hibernation mode motor switched off, cyclic restart active
06 Energy-saving mode motor restarts
07 Hibernation mode supplies the total setpoint of the ramp-function generator
08 Hibernation mode bypasses the ramp-function generator in the setpoint channel
Advanced commissioning
6.9 Energy saving
343