Summary of Contents for Siemens SIMATIC ET 200pro FC-2
Page 3
Fundamental safety ___________________ instructions ___________________ Introduction ___________________ SIMATIC Description ___________________ Installation SIMATIC ET 200pro FC-2 SIMATIC ET 200pro FC-2 converter ___________________ Configure the hardware ___________________ Commissioning Operating Instructions ___________________ Advanced commissioning ___________________ Backing up data and series commissioning ___________________ Repair...
Page 4
Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems.
4.10 Wiring the ET200pro system ....................52 4.11 Mounting ET 200pro FC-2 fail-safe devices ................56 4.11.1 Mounting the bus module and the repair switch ..............57 SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Page 6
Technological unit of the technology controller ..............115 7.6.4 Setting the system of units and technology unit ..............115 Safe Torque Off (STO) safety function ................117 SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Page 7
Motor temperature monitoring using a temperature sensor ..........176 7.16 Motor protection by calculating the temperature ..............180 7.17 Breakdown protection ......................182 7.18 Efficiency optimization ......................183 7.19 PROFIenergy profile for PROFINET ..................186 SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Page 8
Pulse frequency and current reduction ................247 11.5 Electromagnetic compatibility of the converters ..............248 11.5.1 Electromagnetic compatibility ....................248 11.5.2 Definition of EMC environment and EMC classes ............... 248 SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Page 9
Documenting the settings for the basic functions, firmware V4.4 ... V4.7 SP6 ....271 Manuals and technical support ..................... 272 A.5.1 Manuals for your inverter ...................... 272 A.5.2 Product Support ........................273 Index..............................275 SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Page 10
Table of contents SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
The required short-circuit current can be too low, especially for TT supply systems. SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Page 12
• Ensure compliance with the limit values specified in the technical data during transport, storage and operation. • Do not use any damaged devices. SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Page 13
• Tighten all power connections to the prescribed torque. • Check all power connections at regular intervals, particularly after equipment has been transported. SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Page 14
• If you come closer than around 2 m to such components, switch off any radios or mobile phones. • Use the "SIEMENS Industry Online Support app" only on equipment that has already been switched off. SIMATIC ET 200pro FC-2 converter...
As the user you yourself are responsible for ensuring that the products described are operated correctly. Application examples do not relieve you of your responsibility for safe handling when using, installing, operating and maintaining the equipment. SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Siemens’ products and solutions undergo continuous development to make them more secure. Siemens strongly recommends that product updates are applied as soon as they are available and that the latest product versions are used. Use of product versions that are no longer supported, and failure to apply the latest updates may increase customer’s exposure...
Page 19
• Protect files stored on exchangeable storage media from malicious software by with suitable protection measures, e.g. virus scanners. • Protect the drive against unauthorized changes by activating the "know-how protection" drive function. SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
5. Release of environmental pollutants or emissions as a result of improper operation of the system and/or failure to dispose of components safely and correctly 6. Influence of network-connected communication systems, e.g. ripple-control transmitters or data communication via the network SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Page 21
1.5 Residual risks of power drive systems For more information about the residual risks of the drive system components, see the relevant sections in the technical user documentation. SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Page 22
Fundamental safety instructions 1.5 Residual risks of power drive systems SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Download from the Internet DVD that can be ordered End of a handling instruction. ❒ Examples of inverter function symbols See also Overview of the inverter functions (Page 91) SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Meaning of the LEDs on the front of the inverter. System runtime. Faults and warnings. ⑩ The most important technical data of the inverter. ⑪ Setting up the new inverter functions. Application examples. SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Further information is provided on the Internet: OpenSSL (https://www.openssl.org/) Cryptsoft (mailto:eay@cryptsoft.com) Description The SIMATIC ET 200pro FC-2 is a converter that is completely embedded in the distributed I/O system SIMATIC ET 200pro. SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
The inverters with the KC marking on the rating plate satisfy the EMC requirements for South Korea. Eurasian conformity The inverters comply with the requirements of the Russia/Belarus/Kazakhstan customs union (EAC). SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Immunity to voltage drop of semiconductor process equipment. The inverters comply with the requirements of standard SEMI F47-0706. Quality systems Siemens AG employs a quality management system that meets the requirements of ISO 9001 and ISO 14001. Certificates for download ●...
Page 28
The components described below are examples and represent the minimum configuration of a standard frequency converter with the safety function STO. ET 200pro FC-2 with F-RSM Figure 3-1 ET 200pro FC-2 with F-RSM SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Page 29
The converter is connected to the higher-level controller by way of the module bus module and interface module; power and motor are connected using prefabricated cables. Terminating module The ET 200pro bus is terminated with the terminating module SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Page 30
The F-Switch is used in conjunction with the converter only for the module purpose of switching control signals from the higher-level controller through PROFIsafe onto the internal switch-off signals F0 and F1 on the ET 200pro backplane bus. SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Longer lengths up to 15 m can be obtained from our SINAMICS service providers. Motor cables (discontinued but available as spare parts) Order No. Length 6ES7194-1LA01-0AA0 1.5 m 6ES7194-1LB01-0AA0 3.0 m 6ES7194-1LC01-0AA0 5.0 m 6ES7194-1LD01-0AA0 10.0 m SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Page 32
Unused connections without a sealing cap have a degree of protection of only IP20, with a sealing cap it is IP65. Sealing caps for power bus Order No. Quantity 3RK19 02-0CK00 3RK19 02-0CJ00 SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
3.4 Motors and multi-motor drives that can be operated Motors and multi-motor drives that can be operated Siemens motors that can be operated You can connect standard induction motors to the inverter. You can find information on further motors on the Internet: Motors that can be operated (https://support.industry.siemens.com/cs/ww/en/view/100426622)
Page 34
Description 3.4 Motors and multi-motor drives that can be operated SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
2:2005/AMD1:- Section 411 for protection against electric shock. • Observe the installation specifications provided in this manual. • Observe the applicable installation standards. • Ensure the continuity of the protective conductor. SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Mounting the racks The frequency converter is mounted on the wide rack. The following versions are possible: ● Rack, wide ● Rack, compact-wide. SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Page 37
Installation 4.2 Mounting the racks Dimensions Figure 4-1 Dimensional drawing of compact-wide rack SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Page 38
Installation 4.2 Mounting the racks Figure 4-2 Dimensional drawing of wide module rack SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Page 39
5. Connect the opposite end of the grounding cable to ground potential. Ensure adequate equipotential bonding. Figure 4-3 Ground the rack You have mounted and grounded the rack. ❒ SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
All recessed head screws on the front: top and bottom, tightening torque 1.5 Nm The PROFIBUS interface module is shown in the following figure. Figure 4-4 Mounting the interface module You have mounted the interface module. ❒ SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
The bus module is fully secured in place when the frequency converter is installed onto the bus module and the fixing screws on the frequency converter housing are fastened into the mounting rail. Figure 4-6 Mounting the bus module SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
1.5 Nm) until all the bus modules are mounted and screwed in place. The terminating module is included in the scope of delivery of the interface module. Figure 4-7 Mounting the terminating module SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
The settings and connections of all communication modules are described in the manual "ET 200pro Distributed I/O Devices" 2. Fastening the connection module with 4 screws. SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Page 44
Figure 4-8 Installing connection module Connection module Interface module Bus module 155 mm for frequency converters Bus terminating module The connection module has now been installed. ❒ SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Prerequisites When removing the device from the packaging, be sure not to touch or damage the rear connections. Place the converter on an even surface only. SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Page 46
2. Holding the converter firmly against the module rack, screw it in place with 4 screws on the top and 4 screws on the bottom. The upper 4 screws simultaneously fasten the bus module. SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Page 47
4.7 Mounting the converter ① Connection module ② Interface module ③ Frequency converter ④ Bus terminating module Figure 4-12 Mounting the frequency converter The converter is mounted. ❒ SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
The ET 200pro FC-2 has a serial optical communication interface with USS protocol for commissioning using the Intelligent Operator Panel. RS232/optical conversion is performed in the cable between the IOP and the frequency converter. SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
The memory card reader can read and write to SD cards with a memory capacity up to 2 GB. The card reader cannot read high capacity memory cards (SDHC or SDXC). SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
IP67 rating. Above the mini USB connection there must be a minimum clearance distance of 50 mm. Otherwise the screw plug cannot be removed. SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
• Power down the converter and disconnect all power cables from the converter before connecting or disconnecting the motor temperature sensor. • Insulate cables in the motor terminal box that are not used. SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
If the motor holding brake is connected via the Power Module with the converter, the motor holding brake is supplied with 180 V DC and the converter monitors the proper functioning of the brake. SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
⇒ Minimum cross-section of the protective conductor = 16 mm ● Line or motor feeder cable > 35 mm ⇒ Minimum cross-section of the protective conductor = ½ cross-section of the line or motor feeder cable SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
● X1 line supply system input ● X2 motor connector (the cables for both the brake and the temperature sensor are integrated) ● X3 looped-through line supply system SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Page 55
• Power down the converter and disconnect all power cables from the converter before connecting or disconnecting the motor temperature sensor or the motor holding brake. • Insulate cables in the motor terminal box that are not used. SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Page 56
Due to their design features, it is possible that these devices cannot be installed in accordance with the National Electrical Code (NFPA70). Note It is only permissible to use temperature-resistant copper cables for at least 75 °C. SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Page 57
A metallic connector enclosure must be used for connecting. The shield of the motor cable must be connected to a large area of the motor housing (for EMC reasons). SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
1. Module rack 2. Interface module 3. Bus module for F-RSM or F-Switch 4. Bus module for frequency converters 5. Termination module 6. Connection module for the interface module SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Make sure that the seal is cleanly seated and that the recessed head screws are tightened with a torque of 1.5 Nm to ensure a tight arrangement. Figure 4-15 Installing the repair switch module Tools required Cross-tip screwdriver, size 2 SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Installing the F-Switch module The F-Switch module is now installed. ❒ Connection module Interface Module F-Switch Module Bus module 155 mm for frequency converter Bus terminating module SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
● STEP 7 Version 5.3 or higher, Service Pack 2 or higher plus the Hardware Support Package (HSP). HSP is downloaded from HW Config in STEP 7. ● Drive ES block library. SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
5. If you enter the name of the head-end station that you installed in the "Search" field in the hardware catalog, and submit with "Enter", then the corresponding folder opens and lists the components that have been installed. SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
This is done by inserting an IM 154. The PROFIBUS address of the ET 200pro station must also be specified in the IM 154. Insert a master system via the context menu of the CPU DP interface. Figure 5-1 Master system SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Page 64
Inserting the ET 200pro system into the master system and setting the PROFIBUS address Figure 5-2 Selecting the ET 200pro from the hardware catalog Figure 5-3 Assigning the slave address on PROFIBUS DP The configuration should now appear as follows: SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Page 65
Frequency converter selection Figure 5-6 Frequency converter in slot Note When engineering a failsafe application, you must insert an F-RSM or F switch in front of the frequency converter. SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Procedure 1. Open the hardware configuration. 2. Select a SIMATIC CPU with PROFINET interface from the hardware catalog. 3. Add a PROFINET IO system to the CPU. SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Page 67
4. Select object properties in the context menu. 5. Create a new network on the "General" tab via the "Properties" button. You have configured the PROFINET controller. ❒ SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Page 68
You have configured the ET 200pro. ❒ Assign device name The IO controller accesses its IO device via the device name. The IP address is assigned permanently to the device name. SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Page 69
2. Select the ET 200pro: "Ethernet node" → "Browse". If there is an online connection to the station, Step 7 lists all reachable stations on the network SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Page 70
2. Drag and drop the inverter to a slot of your choice in the ET 200pro. 3. Enter the addresses of the inputs and outputs. The input and output address must be identical. You have configured the inverter. ❒ SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
● STEP 7 V 5.3 SP3 or higher ● S7 Distributed Safety V5.4 or higher (F Configuration Pack V5.5 SP1 or higher) ● S7 F systems V5.2 SP2 or higher SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Page 72
5.3 Configure the hardware in SIMATIC Manager Procedure 1. Configure an ET 200pro with an IM154-4 interface module 2. Add an F-switch or F-RSM. PROFINET IO PROFIBUS DP SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Page 73
If you are using an F-switch, you must set up the PROFIsafe address on the module and configure it in STEP 7. Figure 5-7 Setting the PROFIsafe address 1018 by way of example SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
OB82. Enable the diagnostic alarm Procedure 1. Open the inverter properties. 2. Enable the inverter’s diagnostic alarm. You have enabled the inverter’s diagnostic alarm. ❒ SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Connected with the frequency converter 6SL3255-0AA00-2CA0 via USB interface (SINAMICS PC Inverter Connection Kit -2) connected with the frequency converter via fieldbus and head module (IM 154-x) SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
5. Save your settings. (Page 193) You have commissioned the inverter. ❒ Preparing for commissioning Overview Before starting commissioning, you must know the answer to the following questions: SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Page 77
● How is the motor connected? Pay attention to the connection of the motor (star connection [Y] or delta connection [Δ]). Note the appropriate motor data for connecting. SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
3. Select the button to restore the factory settings. 4. Enter the password for the safety functions. 5. Confirm that the parameters have been saved (RAM to ROM). SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Page 80
1. Select the "Extras" menu 2. Select the "Parameter settings" menu 3. Select the entry "Restore drive to factory settings" You have reset the inverter to the factory settings. ❒ SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
In all the scenarios, the IOP-2 will always display the appropriate commissioning screens and sequence for the device to which it is connected. Select Wizards Select Basic Commissioning Select Factory Reset (yes or wizard SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Page 82
Input Motor Frequency Input Motor Voltage Input Motor Current Input Power Rating Input Motor Speed Select Technology Applica- Select required Motor Data Select Macro Source tion ID function SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Page 83
Input Encoder Pulses per rev Select Macro Source Input Maximum Speed Input Ramp-up time Input Ramp-down time Select Motor Temperature Select Motor Holding Brake Input Minimum Motor Spped Sensor option SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Quick commissioning with a PC STARTER and STARTER screen forms STARTER is a PC-based tool to commission Siemens inverters. There are two methods of commissioning when using STARTER: ● You connect the computer, on which STARTER is installed, directly to the inverter via an appropriate USB cable ●...
3. The PC operating system installs the USB driver when you are connecting the inverter and PC together for the first time. 4. Press the "Accessible nodes" button. SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Page 86
1. Set the "Access point" to "DEVICE (STARTER, Scout)" and the "PG/PC interface" to "S7USB". 2. Press the "Update" button. You have set the USB interface. ❒ STARTER now shows the inverters connected via USB. SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
4. When you are online, double-click on "Control Unit". 5. Start the commissioning wizard: You have started the quick commissioning of the inverter. ❒ 6.6.2.4 Carrying out quick commissioning Procedure Select the control mode. SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Page 88
Vector control typically achieves a torque accu- • racy of ± 5% for 10% … 100% of the rated speed Max. output fre- 550 Hz 240 Hz quency SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Page 89
Exit basic commissioning. You have entered all of the data that is necessary for the quick commissioning of your inverter. ❒ SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
● The PC and inverter are connected to each other online. Procedure 1. Open the control panel. 2. Assume master control for the inverter. 3. Set the "Enable signals" SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Page 91
Quick commissioning has been completed once the motor data identification has been successfully completed. SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Motor holding brake (Page 108) You can select in which physical units the inverter represents its associated values. Selecting physical units (Page 112) SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Page 94
Motor protection by calculating the temperature (Page 180) The monitoring of the driven load prevents impermissible operating modes, e.g. dry-running of a pump. Breakdown protection (Page 182) SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Page 95
In the partial load range, the efficiency optimization for standard induction motors reduces the losses in the motor. Efficiency optimization (Page 183) The inverter supports the PROFIenergy profile. PROFIenergy profile for PROFINET (Page 186) SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
In order to be able to respond to external commands, you must set the command interface so that it fits your specific application. Tools To change the function settings, you can use an operator panel or a PC tool, for example. SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Page 97
The motor is still switched on. The inverter brakes "Enable operation" command is always active in the motor with the OFF3 ramp-down time. the inverter factory setting. SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Page 98
Further information You will find additional information in function diagram 2610 of the List Manual. SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Telegrams for cyclic communication Table 7- 3 Explanation of the abbreviations Abbreviation Explanation STW1 Control word 1 ZSW1 Status word 1 NSOLL_A Speed setpoint NIST_A Speed actual value SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
For additional information, please refer to the List Manual in function diagrams 2468 and 2470. 7.4.1.1 Control and status word 1 The control and status words fulfill the specifications of PROFIdrive profile version 4.1 for the "closed-loop speed controlled" mode. SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Page 102
Increase the setpoint saved in the motorized potentiometer. p1035[0] = r2090.13 1 = MOP down Reduce the setpoint saved in the motorized potentiometer. p1036[0] = r2090.14 Reserved SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
With the appropriate converter settings, these interconnections can be changed. Extend telegram The telegram can be extended, by "attaching" additional signals. SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
STOP condition, as otherwise, faults can occur when executing the tasks from the control system and from STARTER/SCOUT. SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Page 105
81 hex: Inverter was not able to completely execute the read request. 01 hex (ID of drive objects, at G120 al- Number of parameters (m) ways = 1) (identical to the read request) SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Page 106
0001 hex ... FFFF hex Parameter number 0001 hex ... FFFF hex Number of the 1st index … … Address, parameter 2 … … … … Address, parameter m … SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Page 107
Only for "Error" - error value 2 Error value 2 is either zero, or it contains the number of the first index where the error oc- curred. Values, parameter 2 SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Page 108
Change request is only possible if the inverter is ready (p0010 = 0). 72 hex Change request is only possible for a parameter reset (restore to factory setting) (p0010 = 30). SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Page 109
CC hex Change request not permitted (change is not permitted as the access code is not available) See also STEP 7 program example for acyclic communication (Page 258) SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Page 111
Controlling the motor holding brake after OFF2 After the OFF2 command, the inverter issues the signal to immediately close the motor holding brake, irrespective of the motor speed. SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Page 112
– p1216 ≥ mechanical opening time of the motor holding brake – p1217 > mechanical closing time of the motor holding brake 5. Switch on the motor. SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Page 113
> braking signal relay runtimes + brake release time p1217 Motor holding brake closing time (factory setting 0.1 s) p1217 > braking signal relay runtimes + brake closing time r0052.12 "Open motor holding brake" command SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
● The repeated change of the unit (e.g.: Percent → physical unit 1 → physical unit 2 → percent) may lead to rounding errors. Reference variables for unit changeover p2000 Reference frequency/speed p2001 Reference voltage SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Some physical units depend on the system of units selected (SI or US), for example the power [kW or hp] or the torque [Nm or lbf ft]. You can select in which system of units the converter represents its physical values. SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Page 116
The parameters associated with the selection of a physical unit, belong to different groups of units. You can find the associated group of units in the List Manual for each parameter. Example: r0333 belongs to unit group 7_4. SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Select the online mode or the offline mode using the adjacent buttons. STARTER indicates whether you change the settings online in the converter or offline in the SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Page 118
The inverter signals that offline, other units and process variables are set than in the inverter itself. 8. Accept these settings in the inverter. You have selected the motor standard and system of units using STARTER. ❒ SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
If the motor is still rotating when STO is selected, then it coasts down to standstill. The STO safety function is standardized The STO function is defined in IEC/EN 61800-5-2: SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Page 120
It is permissible that you switch of the converter supply voltage as well. However, this measure to reduce risk is not specified. SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Table 7- 14 STARTER commissioning tool (PC software) Download Order number STARTER 6SL3255-0AA00-2CA0 (http://support.automation.siemens.com/WW/v PC Connection Kit, includes STARTER DVD and iew/en/10804985/130000) USB cable SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Protection of the settings from unauthorized changes Description p9761 Entering a password (factory setting 0000 hex) No password set 1 … FFFF FFFF: Password is set p9762 New password p9763 Password confirmation SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Basic functions via onboard terminals has been enabled p9761 Enter a password (factory setting: 0000 hex) Permissible passwords lie in the range 1 … FFFF FFFF. p9762 New password p9763 Password confirmation SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
You have interconnected the "STO active" checkback signal. After STO has been selected, the inverter signals "STO active" to the higher-level control. ❒ Parameter Description r9773.01 1 signal: STO is active in the drive SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Inverter response to the off test of the F0 bus In order to avoid an undesirable inverter response, a signal filter in the inverter suppresses the off test of the F0 bus. SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Interconnect this signal with an inverter signal of your choice. 4. Close the screen form. You have set the forced checking procedure (test stop) for the Basic Functions. ❒ SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
3. If the password is the factory default, you are prompted to change the password. If you try to set a password that is not permissible, the old password will not be changed. SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
The acceptance test of the inverter checks whether the integrated drive safety functions are set up correctly for the planned safety function of the machine. Recommended acceptance test (Page 267) SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Page 129
Inverter firmware update. Supplement firmware version • in the inverter data Log the new checksums • Countersignature. • SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Page 130
– Template for the machine documentation: de_G120x_Dokumentation_Maschine: German template. en_G120x_Documentation_machine: English template. – Report of the settings for the basic functions, as of firmware version V4.4: de_G120x_Basic_V4.4…: German report. en_G120x_Basic_V4.4…: English report. SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Acceptance tests for the safety functions (Page 267) Setpoints 7.8.1 Overview The inverter receives its main setpoint from the setpoint source. The main setpoint generally specifies the motor speed. SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Page 132
● When the technology controller is active and appropriately interconnected, its output specifies the motor speed. ● When jogging is active. ● When controlling from an operator panel or the STARTER PC tool. SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Signal source for scaling the main setpoint Factory setting: 1 r1073 CO: Main setpoint active Displays the active main setpoint p1075[0…n] CI: Supplementary setpoint Signal source for the supplementary setpoint Factory setting: 0 SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
The "Motorized potentiometer" function emulates an electromechanical potentiometer. The output value of the motorized potentiometer can be set with the "higher" and "lower" control signals. Figure 7-16 Motorized potentiometer as setpoint source SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Page 135
Start value that is effective when the motor is switched on. start value [rpm] Factory setting: 0 rpm p1047 MOP ramp-up time [s] MOP ramp-up time Factory setting: 10 s SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Page 136
CI: Supplementary setpoint Signal source for the supplementary setpoint Factory setting: 0 p1076[0…n] CI: Supplementary setpoint Signal source for scaling the supplementary setpoint scaling Factory setting: 0 SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Page 137
Signal source for the setting value setting value Factory setting: 0 Further information For more information about the motorized potentiometer, refer to function diagram 3020 in the List Manual. SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Fixed speeds as setpoint source Table 7- 17 Setting the fixed speed as a setpoint source Parameter Remark p1070 = 1024 Main setpoint Interconnecting the main setpoint with fixed speeds. SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
● The "Ramp-function generator" function prevents the setpoint from suddenly changing. As a consequence, the motor accelerates and brakes with a reduced torque. Figure 7-21 Setpoint processing in the inverter SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Set the corresponding parameter to a value = 1 to permanently block directions of rotation. Table 7- 19 Example of settings to inhibit the direction of rotation Parameter Remark p1110 = 1 Inhibit negative direction Negative direction is permanently inhibited. SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
The extended ramp-function generator not only limits the acceleration, but by rounding the setpoint, also acceleration changes (jerk). This means that the motor does not suddenly generate a torque. SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Page 144
The ramp-up and ramp-down times of the motor are increased by the rounding times: ● Effective ramp-up time = p1120 + 0.5 × (p1130 + p1131). ● Effective ramp-down time = p1121 + 0.5 × (p1130 + p1131). SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Page 145
You can find more information in function diagram 3070 and in the parameter list of the List Manual. Setting the extended ramp-function generator Procedure 1. Enter the highest possible speed setpoint. 2. Switch on the motor. SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Page 146
Up ramp scaling (factory setting: 1) Signal source for scaling the acceleration ramp. p1139 Deceleration ramp scaling (factory setting: 1) Signal source for scaling the deceleration ramp. SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
❒ Further information is provided on the Internet: FAQ (https://support.industry.siemens.com/cs/ww/en/view/82604741) 7.10 PID technology controller Overview The technology controller controls process variables, e.g. pressure, temperature, level or flow. SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Page 148
To change the function settings, you can use an operator panel or a PC tool, for example. Function description Function diagram The technology controller is implemented as a PID controller (controller with proportional, integral, and derivative action). SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Page 149
The settings required as a minimum are marked in gray in the function diagram: ● Interconnect setpoint and actual values with signals of your choice ● Set ramp-function generator and controller parameters K and T SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Page 150
You must change this limit, depending on your particular application. Example: The output of the technology controller supplies the speed setpoint for a pump. The pump should only run in the positive direction. SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
● Enable, limiting the controller output and fault response FAQ (http://support.automation.siemens.com/WW/view/en/92556266) 7.11 Motor control The inverter has two alternative methods to control (closed loop) the motor speed: ● U/f control ● Vector control SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
For operation of the motor with U/f control, you must set at least the subfunctions shown with a gray background in the figure to adapt them to your application: ● V/f characteristic ● Voltage boost SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
When the maximum output voltage is reached, the inverter only increases the output frequency. At this point, the motor enters the field weakening range: At constant torque, the slip decreases quadratically as the speed increases. SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Setting the voltage boost for U/f control The inverter boosts the voltage corresponding to the starting currents p1310 … p1312. Figure 7-27 The resulting voltage boost using a linear characteristic as example SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Page 157
("break loose torque"). You will find more information on this function in the parameter list and in function diagram 6301 in the List Manual. SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
I (torque setpoint). The closed-loop control responds to a higher torque setpoint by adding a higher slip frequency to the output frequency. The higher output SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
● The inverter does not reach the set torque limits during acceleration ● You operate the motor in the range 40 % … 60 % of its rated speed SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Page 160
Optimizing the speed controller Requirements ● Torque precontrol is active: p1496 = 100 %. ● The load moment of inertia is constant and independent of the speed. SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
(p1120 and p1121) back to the value before optimization. 7.11.2.4 Friction characteristic Function In many applications, e.g. applications with geared motors or belt conveyors, the frictional torque of the load is not negligible. SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Page 162
When the inverter has determined all the intermediate points of the friction characteristic without fault code F07963, the inverter stops the motor. You have recorded the friction characteristic. ❒ SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Page 163
At the start of automatic plotting, the inverter accelerates the motor up to the speed = p3829 und keeps the speed constant for this time. Further information on this topic is provided in the List Manual. SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
From the actual speed, the actual motor torque and the frictional torque of the load, the inverter calculates the total moment of inertia of the load and motor. Figure 7-33 Overview of the function of the moment of inertia estimator SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Page 165
● Acceleration × moment of inertia (r1493) < 0.9 × p1560 How does the inverter calculate the moment of inertia? Figure 7-35 Calculating the moment of inertia SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Page 166
Moment of inertia J = p5312 × load torque M + p5313 ● In a negative direction of rotation: Moment of inertia J = p5314 × load torque M + p5315 SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Page 167
Moment of inertia ratio, total to motor (factory setting: 1) Ratio of moment of inertia load + motor to moment of inertia of motor without load p1400 Speed control configuration SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Page 168
Moment of inertia estimator accelerating torque threshold value (factory setting: 10%) p1561 Moment of inertia estimator change time The lower that p1561 or p1562 is, the inertia (factory setting: 500 ms) shorter the moment of inertia estimator SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
DC braking is used for applications where the motor must be actively stopped; however, neither an inverter capable of energy recovery nor a braking resistor is available. SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Page 170
1. The motor speed has exceeded the starting speed. 2. The inverter activates the DC braking as soon as the motor speed falls below the starting speed. SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Page 171
1. The higher-level control switches off the motor (OFF1 or OFF3). 2. The motor brakes along the down ramp to the speed for the start of DC braking. 3. DC braking starts. SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Page 172
The inverter's List Manual lists in the "Faults and alarms" list the possible fault responses for every fault. Entry "DCBRK" means that you may set DC braking as response for this fault. SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Limiting feedback with vector control (p1300 ≥ 20) p1531 Power limit generative (factory setting: -0.01 kW) The inverter calculates the parameter based on the quick commissioning or with p0340 = 5. SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Speed output of the I-max controller Shows the amount to which the I-max controller reduces the speed. For more information about this function, see function diagram 6300 in the List Manual. SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
● In vector control, the inverter reduces the output current. ● In U/f control, the inverter reduces the speed. Once the overload condition has been removed, the inverter re-enables the output current or speed. SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Page 176
Also see p0290 = 2. Once the overload condition has been removed, the inverter increases the pulse frequency back to the pulse frequency setpoint p1800. SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Page 177
If it is not possible to temporarily reduce the pulse frequency, or the measure cannot prevent a power unit thermal overload, then the inverter switches off the motor with fault F30024. SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
• Do not earth cables that are not used. Temperature switch The inverter interprets a resistance ≥ 100 Ω as being an opened temperature switch and responds according to the setting for p0610. SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Page 179
– Short-circuit: The inverter interprets a resistance < 50 Ω as a short-circuit and responds with alarm A07015. After 100 milliseconds, the inverter responds with fault F07016. SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Page 180
For monitoring the motor temperature with KTY84/PT1000. p0605 Mot_temp_mod 1/2 / sensor threshold and temperature value (factory setting: 145° C) For monitoring the motor temperature with KTY84/PT1000. SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Page 181
0 signal: Enable PTC short-circuit monitoring 1 signal: Disable PTC short-circuit monitoring Additional information on the motor temperature monitoring can be found in function diagram 8016 of the List Manual. SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
After switching the supply voltage on again, the thermal motor model starts with 90 % of the previously saved differ- ence temperature. SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Page 183
Specification of the motor ambient temperature in °C at the instant of the motor data identification. r0632 Mot_temp_mod stator winding temperature [°C] p0640 Current limit [A] Further information is provided in the function charts 8016 and 8017 of the List Manual. SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Motor model fault signal stall detection [%] p2178 Motor stalled delay time (factory setting: 0.01 s) r2198 Status word monitoring 2 r2198.07 = 1: Motor stalled SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
However, in all applications, speed and torque are specified by the driven machine. As a consequence, the remaining variable for the efficiency optimization is the flux. SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Page 186
Qualitative result of efficiency optimization, method 2 Depending on the motor operating point, the inverter either decreases or increases the flux in partial load operation of the motor. SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Page 187
[%] Factory setting: 50 % p3316 Efficiency optimization 2 Maximum limit value for the calculated optimal flux maximum flux limit value [%] Factory setting: 110 % SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Parameter r5600 shows the active PROFIenergy energy-saving mode. Connector parameter r5613 indicates whether the PROFIenergy energy-saving mode is active. You can set additional responses using these parameters. SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Name Domain Class Number Name Active power r0032 Active power smoothed r2004 Power factor r0038 Smoothed power factor 0 … 1 Active energy import r0039[1] Energy accepted SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
This command returns the measured value IDs that can be accessed using the "Get_Measurement_Values" command. ● Get_Measurement_List_with_object_number This command returns the measured value IDs and the associated object number that can be accessed using the "Get_Measurement_Values_with_object_number" command. SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
The settings in the inverter with the same index are called the drive data set. SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Page 192
If you do not switch over the motor data together with the drive data sets (i.e. same motor number in p0826), then the drive data sets can also be switched over in operation. SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Page 193
Source drive data set p0819[1] Target drive data set p0819[2] = 1 Start copy operation For more information, see the List Manual (the parameter list and function diagram 8565). SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Page 194
Advanced commissioning 7.20 Switchover between different settings SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
2. Back up the settings of the first inverter to an external storage medium. 3. Transfer the settings from the first inverter to an additional inverter via the data storage medium. SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
● Know-how protection is only possible with one of the recommended memory cards. ● Under certain circumstances, memory cards from other manufacturers do not support writing or reading data from/to the inverter. SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
The inverter always saves its settings in its internal memory as well as to the memory card. The slot for the memory module is located at the rear of the inverter. SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
5. Go offline: You have backed up the settings with STARTER. ❒ PC/PG → inverter The procedure depends on whether you also transfer settings of safety functions or not. SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Page 199
2. Press the "Activate settings" button. 3. To save the data in the inverter, click the "Copy RAM to ROM" button: 4. Go offline: 5. Switch off the inverter power supply. SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
1. Connect the operator panel to the inverter. 2. Start data transfer in the menu "UP/DOWNLOAD" - "Drive to panel". You have backed up the settings to the IOP-2. ❒ SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Write protection is applicable for all user interfaces: ● Operator Panel BOP-2 and IOP-2 ● STARTER PC tool ● Parameter changes via fieldbus No password is required for write protection. SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Page 202
● Safely removing the memory card (p9400) ● Restoring the factory setting ● Transfer the settings from an external data backup, e.g. upload into the inverter from a memory card. SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
You can hide know-how protected parameters in the expert list of STARTER using the "Without know-how protection" display filter. ● The values of monitoring parameters r … remain visible. ● STARTER does not display any screen forms. SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Page 204
Commissioning know-how protection 1. Check as to whether you must extend the exception list. List of exceptions (Page 203) 2. Activate the know-how protection. Know-how protection (Page 204) SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
KHP OEM exception list number of indices for p7764 (factory setting 1) p7764 KHP OEM exception list (factory setting [0] 7766, [1 …499 ] 0) p7766 is the password for know-how protection SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
5. If, in spite of active know-how protection, you wish to permit diagnostic functions, activate option "Allow diagnostic functions (trace and measuring functions)". 6. Click on "Define" SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Page 207
"Know-how protection drive unit → Change password ...". Deactivating know-how protection, deleting a password Procedure with STARTER 1. Go online with STARTER. 2. Select the required inverter in the project. SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Page 208
KHP configuration p7766[0...29] KHP password input p7767[0...29] KHP password new p7768[0...29] KHP password confirmation p7769[0...20] KHP memory card reference serial number r7843[0...20] Memory card serial number SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
• Only commission the following persons to repair the inverter: – Siemens customer service – A repair center that has been authorized by Siemens – Specialist personnel who are thoroughly acquainted with all the warnings and operating procedures contained in this manual.
This could result in unexpected behaviour of the replacement converter. • If the firmware version of the replacement converter is different, then you have to recommission the converter from the default factory settings. SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Page 211
Ensure that the weight of the converter is supported during this • step so the converter does not fall off the DIN rail when the screws are removed. SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Page 212
The weight of the converter must be supported during the • fixing process to ensure that the converter is fitted correctly to the DIN rail. The torque for the fixing screw is: 1.5 Nm • SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Page 213
When recommissioned, if the alarm A01028 is not present after the power-cycle of the converter the new param- • eter settings have been accepted. Perform a reduced acceptance test as described in the following procedure. • You have now replaced the converter. ❒ SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Inverter firmware update. Supplement firmware version • in the inverter data Log the new checksums • Countersignature. • SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
"USER" directory. You have prepared the memory card for the firmware upgrade or downgrade. ❒ Memory cards that can be ordered: Spare parts and accessories (Page 29) SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Page 216
Repair 9.3 Firmware upgrade and downgrade Overview of firmware upgrades and downgrades User actions Inverter response Figure 9-2 Overview of the firmware upgrade and firmware downgrade SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
The transfer takes between 5 and 10 minutes. While data is being transferred, the LED RDY on the inverter stays red. The SAFE LED flashes with a variable frequency. SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Page 218
• If the settings are not suitable for the inverter, remove the memory card. – You remove the memory card. In this case, the converter retains its settings: SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Page 219
14. Reconnect all connectors. 14. Switch on the 24 V inverter supply volt- age. 15. If the firmware upgrade was successful, the inverter LED RDY turns green after several seconds. SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
5. Plug the inverter into the ET 200pro station and tighten two of the fixing screws so that the inverter can no longer unintentionally become detached from the bus module. 6. Switch on the 24 V inverter supply voltage. SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Page 221
Power supply failure during the transfer The inverter firmware will be incomplete if the power supply fails during the transfer. • Start again with Step 1 of these instructions. SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Page 222
• If the settings are not suitable for the inverter, remove the memory card. – You remove the memory card or the memory card does not contain any data backup. In this case, the inverter retains its settings. SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Page 223
15. If the firmware upgrade was successful, backup to the inverter. the inverter LED RDY turns green after several seconds. Transferring the settings from the memory card (Page 195) SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
– For a downgrade at least V4.7. ● Have you inserted the card properly? ● Does the card contain the correct firmware? ● Repeat the appropriate procedure. SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
– Interface for STARTER ● Identification & maintenance data (I&M) If requested, the inverter sends data to the higher-level control via PROFIBUS or PROFINET: – Inverter-specific data – Plant-specific data SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Converter is waiting for a power cycle after firmware update YELLOW - fast The converter has detected a safety function fault and initiated a STOP response Firmware update is running SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
● r3121[0 … 63]: Components which are involved with the alarm (only for PROFINET) The inverter transfers the messages in the sequence in which they occurred The control generates the time stamp when the messages are received SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Page 228
Channel temporarily not available Reading out diagnostics data The control requests the diagnostics data from the inverter using "Read data set", e.g. using a read record with index 800C hex. SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Page 229
Manuals for your inverter (Page 272) You can find more information on channel-related diagnostics and the diagnostics alarm with DS0 / DS1 in the following tables. SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Page 230
Fault 1 in actuator/sensor 001F Channel temporarily not available When several faults are allocated at one inverter with the same message class, then only one mes- sage is displayed. SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Page 231
0: No fault is active 1: DS1 exists 1: Fault is active Internal fault Type of class module = 0011 (distributed) 0: No fault is active 1: Fault is active SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
System diagnostics by means of standardized functions Prerequisites 1. When configuring the interface module, the diagnosis must be released. 2. When configuring the converter, the diagnosis must be released. SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
– Display on the operator panel with Axxxxx – Display in STARTER Alarm code or alarm value describe the cause of the alarm. Alarm buffer Figure 10-2 Alarm buffer SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Page 235
"up". 4. The inverter saves the received alarm as the latest alarm in the alarm buffer. SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Page 236
Setting the message type for the selected alarm 1: Fault 2: Alarm 3: No message You will find details in function diagram 8075 and in the parameter description of the List Manual. SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
In the fault buffer, the faults are sorted according to "Fault time received". If the fault buffer is completely filled and an additional fault occurs, then the inverter overwrites the values with Index [7]. SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Page 238
The "Fault time removed" of the faults that have not been removed retains the value = 0. The fault history can contain up to 56 faults. Deleting the fault history To delete all faults from the fault history, set parameter p0952 to zero. SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Page 239
You can change up to 20 different faults into an alarm, or suppress faults: p2119[0 … 19] Setting the message type Setting the message type for the selected fault 1: Fault 2: Alarm 3: No message SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
You will find details in function diagram 8075 and in the parameter description of the List Manual. 10.6 List of alarms and faults Axxxxx Alarm Fyyyyy: Fault SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Page 241
Then reset the inverter to the factory setting again. F01662 CU hardware fault Switch CU off and on again, upgrade firmware or contact technical sup- port. SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Page 242
F07330 Search current measured too low Increase search current (p1202), check motor connection. SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Page 243
F07862 F07900 Motor blocked Check that the motor can run freely. Check the torque limits (r1538 and r1539). F07901 Motor overspeed Check whether the motor is overloaded. SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Page 244
IP address, subnet mask or default gateway is not correct. • IP address or station name used twice in the network. • Station name contains invalid characters. • SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Page 245
Check the power cable connections. • Check the motor. • Check the current transformer. • Check the cables and contacts of the brake connection (a wire might • be broken). SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Page 246
Replace Power Module or contact technical support. A30920 Temperature sensor fault Check that the sensor is connected correctly. For further information, please refer to the List Manual. SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
DC 200 Maximum current of the brake control Pulse frequency (factory setting) Installation altitude above sea level 2000 Efficiency η 95 … 97 Power factor Mechanical data SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
A clearance of 35 mm must be kept above and below the components of the frequency converter from other devices or components in order to ensure that convection can take place unhindered. SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Pulse frequency and current reduction Relationship between pulse frequency, temperature and output base-load current Figure 11-1 Power derating in relation to the ambient temperature and pulse frequency SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Definition of EMC environment and EMC classes Classification of EMC behavior The EMC environment and the EMC classes are defined in the EMC product standard EN 61800-3 as follows: SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Page 251
Note A specialist is a person or organization with the necessary skills to install and/or commission a power drive system (PDS) including its EMC aspects. SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
System interruptions and EN 61000-2-1 100 % voltage dip for 3 ms voltage dips 30 % voltage dip for 10 ms 60 % voltage dip for 100 ms SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Page 254
2) Shutdown on fault F00003 "Undervoltage" 3) Shutdown on fault F00002 "Overvoltage" The requirements of the product standard for a drive system, according to C3, are fulfilled. SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
4 kV, contact discharge Interference Burst EN 61000-4-4 2 kV electric power cable pulses 1 kV control cable Voltage surge EN 61000-4-5 2 kV electric power cable (phase - ground) SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Page 256
The requirements of the generic standards in respect of interference immunity are met. The required values for interference emission are complied with if installation takes place according to EMC installation guidelines. SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Control and status words consist of a high byte and a low byte. A SIMATIC control interprets words differently than the inverter: The higher and lower-order bytes are interchanged when they are transferred. See also the following program example. SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Bit in Significance Bit in Bit in Bit in Inputs STW1 ON/OFF1 E0.0 OFF2 OFF3 Operation enable Ramp-function generator enable Start ramp-function generator Setpoint enable Acknowledge fault E0.6 SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Page 259
Significance Bit in Bit in Bit in Inputs STW1 Jog 1 Jog 2 PLC control Setpoint inversion Irrelevant Motorized potentiometer ↑ Motorized potentiometer ↓ Data set changeover SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
M9.3 Displays the write process The number of simultaneous requests for acyclic communication is limited. More detailed infor- mation can be found under http://support.automation.siemens.com/WW/view /de/15364459 (http://support.automation.siemens.com/WW/vie w/en/15364459). SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Page 261
With acyclic communication via PROFINET, you must replace the system functions with standard function blocks as follows: • SFC 58 → SFB 53 • SFC 59 → SFB 52 SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Page 262
After the read request and a waiting time of one second, the controller takes the parameter values from the inverter via SFC 59 and saves them in DB 2. SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Page 263
SFC 58 copies the specifications for the parameters to be written from DB 3 and sends them to the inverter. The inverter blocks other write jobs while this write job is running. SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
START, the results remain under the "Measurements" tab with data and time. When terminating STARTER or under the "Measurements" tab, you can save the measurement results in the *.trc format. SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Page 265
Using , select "Trigger to variable - bit pattern" Using , select the bit parameter Using , open the screen form in which you set the bits and their values for the start condition SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Page 266
1. Insert the memory card into a card reader. 2. Go to the "Measurements" tab in the device trace. 3. Open the read out ACX files with the "Open measurements" button. SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
The signal interconnection of the blocks is realized, contrary to electric circuitry, not using cables, but in the software. Figure A-5 Example: Signal interconnection of two blocks for digital input 0 SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Page 268
Note which changes you make. A subsequent analysis of the set signal interconnections is possible only by evaluating the parameter list. We recommend that you use the STARTER commissioning tools for setting the signal interconnections. SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Note Non-critical alarms The following alarms are issued following each system ramp-up and are not critical for acceptance: • A01697 • A01796 SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
If a mechanical brake is not available, the motor coasts • down. A mechanical brake brakes the motor and holds it to en- sure that it remains at a standstill. SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Overview diagram of the machine and/or system: Inverter data The inverter data include the hardware version of the safety-relevant inverter. Labeling the drive Article number and hardware version of the inverter SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
Page 272
Circuit diagrams Countersignatures Commissioning engineer The commissioning engineer confirms that the tests and checks listed above have been correctly executed. Date Name Company/dept. Signature … … … … SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
SI Safe Stop 1 delay time p9652 <p9652_v> SI forced dormant error detection timer p9659 <p9659_v> SI forced checking procedure STO via PM terminals time p9661 <p9661_v> SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...
<r9782[1]_v> Manuals and technical support A.5.1 Manuals for your inverter Manuals with additional information that can be downloaded ● Getting Started SIMATIC ET 200pro FC-2 (https://support.industry.siemens.com/cs/ww/en/view/109478674) Installing the inverter ● SIMATIC ET200 proFC-2 operating instructions (https://support.industry.siemens.com/cs/ww/en/view/109478246) Installing, commissioning and maintaining the inverter. Advanced commissioning (this manual) ●...
Appendix A.5 Manuals and technical support ● SIMATIC ET 200pro FC-2 List Manual (https://support.industry.siemens.com/cs/ww/en/view/109478711) Parameter lists, alarms and faults. Graphic function diagrams ● Operating instructions IOP-2 (https://support.industry.siemens.com/cs/ww/en/view/109752613) Operating the inverter with an Operator Panel A.5.2 Product Support You can find additional information about the product on the Internet: Product support (https://support.industry.siemens.com/cs/ww/en/)
Page 276
Appendix A.5 Manuals and technical support SIMATIC ET 200pro FC-2 converter Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF...