The following table lists the temperature measurement range of the NZ2FTS-60RD4.
Value in C
Measurement
range
0.1C resolution
Pt100
-2000 to 8500
-2040
8540
32767
Pt200
-2000 to 8500
-2040
8540
32767
Pt500
-2000 to 8500
-2040
8540
32767
Pt1000
-2000 to 8500
-2040
8540
32767
Ni100
-600 to +2500
-640
2540
32767
Ni120
-800 to +2600
-840
2640
32767
Ni200
-600 to +2500
-640
2540
32767
Ni500
-600 to +2500
-640
2540
32767
Ni1000
-600 to +2500
-640
2540
32767
Cu10
-1000 to +2600
-1040
2640
32767
18 TEMPERATURE INPUT MODULE
502
18.1 NZ2FTS-60RD4
Value in F
0.1/digit
-3280 to 15620
-3352
15692
32767
-3280 to 15620
-3352
15692
32767
-3280 to 15620
-3352
15692
32767
-3280 to 15620
-3352
15692
32767
-760 to 4820
-832
4892
32767
-1120 to +5000
-1192
5072
32767
-760 to 4820
-832
4892
32767
-760 to 4820
-832
4892
32767
-760 to 4820
-832
4892
32767
-1480 to 5000
-1552
5072
32767
Value in K
0.1K/digit
732 to 11232
692
11272
32767
732 to 11232
692
11272
32767
732 to 11232
692
11272
32767
732 to 11232
692
11272
32767
2132 to 5232
2092
5272
32767
1932 to 5332
1892
5372
32767
2132 to 5232
2092
5272
32767
2132 to 5232
2092
5272
32767
2132 to 5232
2092
5272
32767
1732 to 5332
1692
5372
32767
Range
-200 to +850
Underload
Overload
Disconnection
-200 to +850
Underload
Overload
Disconnection
-200 to +850
Underload
Overload
Disconnection
-200 to +850
Underload
Overload
Disconnection
-60 to 250
Underload
Overload
Disconnection
-80 to 260
Underload
Overload
Disconnection
-60 to 250
Underload
Overload
Disconnection
-60 to 250
Underload
Overload
Disconnection
-60 to 250
Underload
Overload
Disconnection
-100 to 260
Underload
Overload
Disconnection