Page 2
IM 155-6 PN ST Interface Module (6ES7155-6AU02-0BN0) Introduction Industrial cybersecurity SIMATIC Product overview Wiring ET 200SP IM 155-6 PN ST Interface Module (6ES7155-6AU02-0BN0) Parameters/address space Interrupts, diagnostics, error, and system messages Equipment Manual Compatibility Operation and maintenance Technical specifications Dimension drawing 11/2023 A5E53132379-AA...
Page 3
Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems.
Table of contents Introduction ............................5 Introduction ........................5 ET 200SP Documentation Guide ................... 6 1.2.1 ET 200SP Documentation Guide ................... 6 1.2.2 SIMATIC Technical Documentation ..................8 1.2.3 Tool support ........................10 MultiFieldbus Configuration Tool (MFCT) ................11 Industrial cybersecurity ........................12 Introduction to industrial cybersecurity ................
Page 5
Table of contents Wiring ..............................30 Pin assignment ........................30 Schematic circuit diagram ....................31 Parameters/address space ........................32 Parameters ........................32 Explanation of parameters ....................32 5.2.1 Configuration control ......................32 Substitute value behavior ....................33 Status of the supply voltage L+ of the I/O modules ............. 34 Interrupts, diagnostics, error, and system messages ................
Purpose of the documentation This equipment manual supplements the ET 200SP Distributed I/O System (http://support.automation.siemens.com/WW/view/en/58649293) system manual. Functions that generally relate to the system are described in the system manual. The information provided in this manual and in the system/function manuals supports you in commissioning the system.
ET 200SP Documentation Guide 1.2.1 ET 200SP Documentation Guide The documentation for the SIMATIC ET 200SP distributed I/O system is arranged into three areas. This arrangement enables you to access the specific content you require. You can download the documentation free of charge from the Internet (https://support.industry.siemens.com/cs/ww/en/view/109742709).
Page 8
You can find the latest Product Information on the ET 200SP distributed I/O system on the Internet. (https://support.industry.siemens.com/cs/de/en/view/73021864) Manual Collection ET 200SP The Manual Collection contains the complete documentation on the SIMATIC ET 200SP distributed I/O system gathered together in one file. You can find the Manual Collection on the Internet.
Industry Online Support International (https://support.industry.siemens.com/cs/ww/en/view/109742705) Watch this short video to find out where you can find the overview directly in Siemens Indus- try Online Support and how to use Siemens Industry Online Support on your mobile device: Quick introduction to the technical documentation of automation products per video (https://support.industry.siemens.com/cs/us/en/view/109780491)
Page 10
Manuals, characteristics, operating manuals, certificates • Product master data You can find "mySupport" on the Internet. (https://support.industry.siemens.com/My/ww/en) Application examples The application examples support you with various tools and examples for solving your automation tasks. Solutions are shown in interplay with multiple components in the system - separated from the focus on individual products.
(https://support.industry.siemens.com/cs/ww/en/view/109767888) SINETPLAN SINETPLAN, the Siemens Network Planner, supports you in planning automation systems and networks based on PROFINET. The tool facilitates professional and predictive dimensioning of your PROFINET installation as early as in the planning stage. In addition, SINETPLAN supports you during network optimization and helps you to exploit network resources optimally and to plan reserves.
MultiFieldbus- and DALI-devices. In addition, the MFCT offers convenient options for mass firmware updates of ET 200 devices with MultiFieldbus- support and reading service data for many other Siemens devices. Functional scope of the MFCT • MultiFieldbus configuration:...
Siemens' products and solutions undergo continuous development to make them more secure. Siemens strongly recommends that product updates are applied as soon as they are available and that the latest product versions are used. Use of product versions that are no longer supported, and failure to apply the latest updates may increase customers' exposure to cyber threats.
Corrective measures for known risks Corrective measures for known risks are announced on the Siemens ProductCERT and Siemens CERT (https://siemens.com/productcert) web page. For more information on SIEMENS ProductCERT, refer to the System Manual. Security checks You can find descriptions of specific security measures, such as cyclic checks of the configuration via checksums, in the Industrial cybersecurity section of the System Manual.
Product overview Properties Article number 6ES7155-6AU02-0BN0 (IM 155-6 PN ST interface module and server module) 6ES7155-6AA02-0BN0 (IM 155-6 PN ST interface module with BusAdapter BA 2×RJ45 and server module) View of the module Figure 3-1 View of the IM 155-6 PN ST interface module Properties The module has the following technical properties: •...
Page 16
The article number is 6ES7155-6AA02-0BN0. A detailed list of the available accessories can be found in the system manual ET 200SP distributed I/O system (http://support.automation.siemens.com/WW/view/en/58649293). Server module The server module is included in the scope of delivery of the interface module and available separately as an accessory.
Page 17
Group diagnostics: missing supply voltage L+. When there are 32 I/O modules, the server module is inserted in slot 33. You can find more information in the Server module (http://support.automation.siemens.com/WW/view/en/63257531) manual. First BaseUnit of an ET 200SP in the configuration Note...
Product overview 3.2 Functions Functions Introduction The interface module supports the following PROFINET IO functions: • Integrated switch with 2 ports • Supported Ethernet services: ICMP, ARP, SNMP, LLDP • Port diagnostics • Disabling ports • Isochronous real-time communication • Minimum update time 1 ms •...
Page 19
GSD file V5.5 SP4 with Portal) as of (http://support.a HSP329 V18 with utoma- HSP 415 tion.siemens.co m/WW/view/en/1 9698639/130000 )/software from a third-party manufacturer Supported Ethernet services: V6.1.0 ICMP, ARP, SNMP, LLDP Port diagnostics V6.1.0...
Page 20
You can find more information on this topic in the STEP 7 online help and: • As of STEP 7 V12 in the PROFINET with STEP 7 V13 (http://support.automation.siemens.com/WW/view/en/49948856) function manual • As of STEP 7 V5.5 in the PROFINET System Description (http://support.automation.siemens.com/WW/view/en/19292127) system manual...
Product overview 3.2 Functions 3.2.1 Supported Ethernet services: ICMP, ARP, SNMP, LLDP Supported Ethernet services: ICMP, ARP, SNMP, LLDP The module supports the following standardized Ethernet services: • ICMP - Internet Control Message Protocol (RFC 792) ICMP is a protocol used to transmit informational and error messages over the Internet protocol.
You can find more information on the configuration of synchronized PROFINET devices in sync domains in the STEP 7 online help and: • As of STEP 7 V12 in the PROFINET with STEP 7 V13 (http://support.automation.siemens.com/WW/view/en/49948856) function manual • As of STEP 7 V5.5 in the PROFINET System Description (http://support.automation.siemens.com/WW/view/en/19292127) system manual 3.2.5...
You can find more information on this topic in the STEP 7 online help and: • As of STEP 7 V12, in the PROFINET with STEP 7 (https://support.industry.siemens.com/cs/ww/en/view/49948856) Function Manual. • As of STEP 7 V5.5 in the PROFINET System Description (http://support.automation.siemens.com/WW/view/en/19292127) System Manual.
You can find more information on this topic in the STEP 7 online help and: • As of STEP 7 V12, in the PROFINET with STEP 7 V13 (http://support.automation.siemens.com/WW/view/en/49948856) Function Manual IM 155-6 PN ST Interface Module (6ES7155-6AU02-0BN0) Equipment Manual, 11/2023, A5E53132379-AA...
If the IO devices were already used in another configuration, reset them to factory settings before reusing them. You can find information on this in the system manual Distributed I/O system ET 200SP (https://support.industry.siemens.com/cs/ww/en/view/58649293). You can find additional information in the STEP 7 online help and as of STEP 7 (TIA Portal) V12 in the PROFINET with STEP 7 (https://support.industry.siemens.com/cs/ww/en/view/49948856) function manual.
Firmware update via PROFINET IO Firmware update via PROFINET IO You can find information on how to perform a firmware update in the ET 200SP Distributed I/O System system manual (https://support.industry.siemens.com/cs/ww/en/view/58649293). 3.2.14 Identification data I&M 0 to I&M 4 Identification data I&M 0 to I&M 4 Identification and maintenance data (I&M data) is information saved on the module.
• PROFINET with STEP 7 V13 (http://support.automation.siemens.com/WW/view/en/49948856) function manual. • System manual PROFINET system description (http://support.automation.siemens.com/WW/view/en/19292127) • PROFIenergy (http://support.automation.siemens.com/WW/view/en/66928686) product information. • Internet (http://www.profibus.com) under Common Application Profile PROFIenergy; Technical Specification for PROFINET; Version 1.0; January 2010; Order No: 3.802.
Reference You can find more information on configuration control • in the ET 200SP distributed I/O system (http://support.automation.siemens.com/WW/view/en/58649293) system manual • on the Internet under the following link: Application collection (http://support.automation.siemens.com/WW/view/en/29430270) • in the STEP 7 online help.
In the case of a pending maintenance alarm, you can read out the service data and make it available to SIEMENS support for queries and product improvement. The service data is read out using the TCP protocol. A connection on port 102 is opened for this.
BusAdapter during operation. Reference You can find more information on the removal/insertion of modules in the system manual ET 200SP distributed I/O system (https://support.automation.siemens.com/WW/view/en/58649293). 3.2.26 Maintenance events Maintenance events A maintenance event indicates an identified maintenance requirement that has no direct influence on the function of the module.
Maximum 10 A permitted Reference You can find more information on accessories and how to connect the interface module in the ET 200SP distributed I/O system (http://support.automation.siemens.com/WW/view/en/58649293) system manual. IM 155-6 PN ST Interface Module (6ES7155-6AU02-0BN0) Equipment Manual, 11/2023, A5E53132379-AA...
Wiring 4.2 Schematic circuit diagram Schematic circuit diagram The following figure shows a block diagram of the IM 155-6 PN ST interface module. ① Switch 24 V DC supply voltage ② ET 200SP backplane bus interface and elec- Mass tronics ③...
196 from the user program in order for the ET 200SP distributed I/O system to operate the I/O modules. Reference You can find more information in the ET 200SP distributed I/O system (http://support.automation.siemens.com/WW/view/en/58649293) system manual and in the STEP 7 online help. IM 155-6 PN ST Interface Module (6ES7155-6AU02-0BN0) Equipment Manual, 11/2023, A5E53132379-AA...
Parameters/address space 5.3 Substitute value behavior Substitute value behavior The substitute value behavior in the ET 200SP distributed I/O system is executed by the IO controller for each slot. The respective output behaves according to its configured substitute value behavior: •...
The "Status of supply voltage L+ of the I/O modules" is configured on the server module. The input data can then be read out on the server module. You will find the relevant description in the Server module (http://support.automation.siemens.com/WW/view/en/63257531) device manual.
Interrupts, diagnostics, error, and system messages Status and error displays LED display The following diagram shows the LED display on the interface module and the BusAdapter. ① RN (green) ② ER (red) ③ MT (yellow) ④ PWR (green) ⑤ LK1 (green) ⑥...
Page 37
Perform a firmware update. If the error persists, contact Siemens Industry Online Support. Replace the interface module. You can read out the service data with TIA Portal as of V18 and MFCT.
Page 38
Interrupts, diagnostics, error, and system messages 6.1 Status and error displays PWR LED on the interface module Table 6- 2 PWR status display on the interface module PWR LED Meaning Remedy Supply voltage not present or too small Check the supply voltage. Supply voltage present LK1/LK2 LED on the BusAdapter Table 6- 3...
Page 39
Interrupts, diagnostics, error, and system messages 6.1 Status and error displays Table 6- 4 Display of error type and error location Sequence Description 1 The ERROR and MAINT LEDs flash 3x at 0.5 Hz Signaling of error type 2 MAINT LED flashes at 1 Hz Display of the error type (decimal) 3 The ERROR and MAINT LEDs flash 3x at 2 Hz Signaling of error location/error code...
CPU S7-1500, the CPU web server and the HMI device. You will find more information on system diagnostics in the Diagnostics (http://support.automation.siemens.com/WW/view/en/59192926) function manual. 6.2.1 Triggering of a diagnostics interrupt Triggering of a diagnostics interrupt For an incoming or outgoing event (e.g.
Interrupts, diagnostics, error, and system messages 6.2 Interrupts 6.2.2 Triggering a hardware interrupt Triggering a hardware interrupt During a hardware interrupt, the CPU interrupts the processing of the user program and processes the hardware interrupt block, e.g. OB 40. The event that triggered the interrupt is entered in the start information of the hardware interrupt block.
Interrupts, diagnostics, error, and system messages 6.3 Alarms Alarms Introduction The ET 200SP distributed I/O system generates the following alarms: • Diagnostic alarms • Maintenance alarms 6.3.1 Diagnostics alarms Actions after a diagnostics alarm There can be more than one diagnostics alarm at the same time. Each diagnostics alarm initiates the following actions: •...
Page 43
If required, the standard can be downloaded from the Internet (http://www.profibus.com). See also PROFINET System Description (http://support.automation.siemens.com/WW/view/en/19292127) From PROFIBUS DP to PROFINET IO (http://support.automation.siemens.com/WW/view/en/19289930) Example application (http://support.automation.siemens.com/WW/view/en/24000238) I/O modules (http://support.automation.siemens.com/WW/view/en/55679691/133300) PROFINET with STEP 7 V11 (http://support.automation.siemens.com/WW/view/en/49948856) IM 155-6 PN ST Interface Module (6ES7155-6AU02-0BN0) Equipment Manual, 11/2023, A5E53132379-AA...
Example: Increased memory the manual and send them to reached requirements due to ex- the SIEMENS Customer Sup- treme overload via port for root cause analysis. PROFINET (denial of service). System events in STEP 7 (TIA Portal) The maintenance information is generated in STEP 7 with the following system events: •...
Verify if the firmware update file you are using comes from a secure source. • Download the firmware again from the Siemens Support Web page. • Repeat the firmware update. IM 155-6 PN ST Interface Module (6ES7155-6AU02-0BN0) Equipment Manual, 11/2023, A5E53132379-AA...
Interrupts, diagnostics, error, and system messages 6.3 Alarms Note Use advanced channel diagnostics instead of manufacturer-specific diagnostics. Manufacturer-specific diagnostics are backwards compatible. 6.3.4 Invalid configuration states of the ET 200SP on PROFINET IO Invalid configuration states The following invalid configuration states of the ET 200SP distributed I/O system lead to the failure of the IO device or prevent the exchange of user data with the I/O modules.
Interrupts, diagnostics, error, and system messages 6.3 Alarms 6.3.5 Failure of supply voltage L+ at BaseUnit BU...D Failure of the supply voltage L+ The I/O modules react as follows to failure of the supply voltage L+ on the BaseUnit BU...D: •...
Compatibility Compatibility between the versions of the IM 155-6 PN ST The table below describes which version you can use in the configuration for which actually plugged version of the IM 155-6 PN ST interface module. Interface modules plugged Interface modules configured 155-6AU00-0BN0 155-6AU01-0BN0 155-...
Page 49
Compatibility • If a potential group is exclusively made up of modules without parameter assignment from the table below, no group diagnostics "Missing supply voltage L+" is signaled for this potential group. Modules Article number DI 8x24VDC ST 6ES7131-6BF00-0BA0 DI 16x24VDC ST 6ES7131-6BH00-0BA0 DI 8x24VDC HF 6ES7131-6BF00-0CA0...
Firmware update with MFCT With MFCT, you can perform firmware updates for modules and interface modules. Information on this is available in the "MultiFieldbus (https://support.industry.siemens.com/cs/ww/en/view/109773209)" function manual in the section "Firmware update with MFCT". IM 155-6 PN ST Interface Module (6ES7155-6AU02-0BN0)
Technical specifications of the IM 155-6 PN ST The following table lists the technical specifications as of the issue date. You can find a data sheet including daily updated technical specifications on the Internet (https://support.industry.siemens.com/cs/de/en/pv/6ES7155-6AU02-0BN0/td?dl=de). Article number 6ES7155-6AU02-0BN0 General information...
Page 52
Technical specifications Article number 6ES7155-6AU02-0BN0 Power loss Power loss, typ. 1.8 W Address area Address space per module 288 byte; For input and output data respectively • Address space per module, max. Address space per station 1 440 byte • Address space per station, max.
Page 53
Technical specifications Article number 6ES7155-6AU02-0BN0 Protocols Modbus TCP Redundancy mode • PROFINET system redundancy (S2) Media redundancy – – MRPD Open IE communication • TCP/IP • SNMP • LLDP Interrupts/diagnostics/status information Status indicator Alarms Diagnostics function Diagnostics indication LED Yes; green LED •...
Page 54
Technical specifications Article number 6ES7155-6AU02-0BN0 Altitude during operation relating to sea level 5 000 m; restrictions for installation altitudes > 2 • Installation altitude above sea level, max. 000 m, see ET 200SP system manual connection method ET-Connection Yes; + 16 ET 200AL modules •...
Dimension drawing This appendix contains a dimension drawing of the module installed on a mounting rail. Always observe the specified dimensions for installation in cabinets, control rooms, etc. Figure A-1 Dimension drawing of the IM 155-6 PN ST interface module (front and side view) IM 155-6 PN ST Interface Module (6ES7155-6AU02-0BN0) Equipment Manual, 11/2023, A5E53132379-AA...