hit counter script

Sel (Select), Mux (Multiplex), And Demux (Demultiplex) Instructions - Siemens SIMATIC S7-1200 System Manual

Hide thumbs Also See for SIMATIC S7-1200:
Table of Contents

Advertisement

8.9.4

SEL (Select), MUX (Multiplex), and DEMUX (Demultiplex) instructions

Table 8- 175 SEL (select) instruction
LAD / FBD
SCL
out := SEL(
g:=_bool_in,
in0:-_variant_in,
in1:=_variant_in);
For LAD and FBD: Click the "???" and select a data type from the drop-down menu.
1
Table 8- 176 Data types for the SEL instruction
Parameter
Data type
G
Bool
IN0, IN1
SInt, Int, DInt, USInt, UInt, UDInt, Real, LReal, Byte, Word, DWord,
Time, Date, TOD, Char, WChar
OUT
SInt, Int, DInt, USInt, UInt, UDInt, Real, LReal, Byte, Word, DWord,
Time, Date, TOD, Char, WChar
Input variables and the output variable must be of the same data type.
1
Condition codes: ENO is always TRUE following execution of the SEL instruction.
Table 8- 177 MUX (multiplex) instruction
LAD / FBD
SCL
out := MUX(
k:=_unit_in,
in1:=variant_in,
in2:=variant_in,
[...in32:=variant_in,]
inelse:=variant_in);
For LAD and FBD: Click the "???" and select a data type from the drop-down menu.
1
S7-1200 Programmable controller
System Manual, V4.2, 09/2016, A5E02486680-AK
Description
SEL assigns one of two input values to parameter OUT, depending
on the parameter G value.
1
Description
MUX copies one of many input values to parameter OUT, depending
on the parameter K value. If the parameter K value exceeds (IN
then the parameter ELSE value is copied to parameter OUT.
Basic instructions
8.9 Word logic operations
Description
0 selects IN0
1 selects IN1
Inputs
Output
n
- 1),
329

Advertisement

Table of Contents
loading

Table of Contents