● With HWTYPE = 5 (submodule):
– All parameters of GEOADDR are evaluated.
– The hardware identifier of the submodule is output.
The AREA parameter of the GEOADDR system data type is not evaluated.
Table 9- 226 Data types for the parameters
Parameter and type
GEOADDR
IN/OUT or
IN ?
RET_VAL
OUT or
RETURN
?
LADDR
OUT
For further information on valid data types, refer to "Overview of the valid data types" in the
STEP 7 online help.
Table 9- 227 Condition codes
RET_VAL*
Explanation
(W#16#...)
0
No error occurred.
8091
Invalid value for in GEOADDR for HWTYPE.
8094
Invalid value for in GEOADDR for IOSYSTEM.
8095
Invalid value for in GEOADDR for STATION.
8096
Invalid value for in GEOADDR for SLOT.
8097
Invalid value for in GEOADDR for SUBSLOT.
* The error codes can be displayed as integer or hexadecimal values in the program editor.
S7-1200 Programmable controller
System Manual, V4.2, 09/2016, A5E02486680-AK
Data type
Description
Variant
Pointer to the structure of the GEOADDR system data type. The
GEOADDR system data type contains the slot information from which the
hardware ID is determined.
Refer to the "GEOADDR system data type (Page 551)" for further infor-
mation.
Int
Output of error information.
HW_ANY
Hardware identifier of the assembly or the module.
The number is automatically assigned and is stored in the properties in
the hardware configuration.
Extended instructions
9.11 Address handling
545