Typical suppressor circuit for DC or relay outputs that switch DC inductive loads
①
②
③
④
Typical suppressor circuit for relay outputs that switch AC inductive loads
①
②
③
S7-1200 Programmable controller
System Manual, V4.2, 09/2016, A5E02486680-AK
1N4001 diode or equivalent
8.2 V Zener (DC outputs),
36 V Zener (Relay outputs)
Output point
M, 24 V reference
See table for C value
See table for R value
Output point
In most applications, the addition of a diode (A)
across a DC inductive load is suitable, but if your
application requires faster turn-off times, then the
addition of a zener diode (B) is recommended. Be
sure to size your zener diode properly for the amount
of current in your output circuit.
Ensure that the working voltage of the metal oxide
varistor (MOV) is at least 20% greater than the nomi-
nal line voltage.
Choose pulse-rated, non-inductive resistors, and
capacitors recommended for pulse applications (typi-
cally metal film). Verify the components meet aver-
age power, peak power, and peak voltage
requirements.