60.02
M/F node address
1...254
60.03
M/F mode
Not in use
DDCS master
DDCS follower
D2D master
D2D follower
DDCS forcing
D2D forcing
60.05
M/F HW connection
Ring
Star
60.07
M/F link control
1...15
Description
Selects the node address of the drive for master/follower
communication. No two nodes on-line may have the same
address.
Note: The allowable addresses for the master are 0 and 1.
The allowable addresses for followers are 2...60.
Node address.
Defines the role of the drive on the master/follower link.
Master/follower functionality not active.
The drive is the master on the master/follower (DDCS) link.
The drive is a follower on the master/follower (DDCS) link.
The drive is the master on the drive-to-drive (D2D) link.
Note: Use the setting
DDCS master
master/follower functionality (see page 74) through the
XD2D connector.
The drive is a follower on the drive-to-drive (D2D) link.
Note: Use the setting
DDCS follower
master/follower functionality (see page 74) through the
XD2D connector.
The role of the drive on the master/follower (DDCS) link is
defined by parameters
60.15 Force master
follower.
The role of the drive on the drive-to-drive (D2D) link is
defined by parameters
60.15 Force master
follower.
Note: Use the setting
DDCS forcing
master/follower functionality (see page 74) through the
XD2D connector.
Selects the topology of the master/follower link.
Note: Use the setting
Star
functionality (see page 74) through the XD2D connector (as
opposed to a fiber optic link).
The devices are connected in a ring topology. Forwarding of
messages is enabled.
The devices are connected in a star topology (for example,
through a branching unit). Forwarding of messages is
disabled.
Defines the light intensity of the transmission LED of RDCO
module channel CH2. (This parameter is effective only when
parameter
60.01 M/F communication port
CH
2. FDCO modules have a hardware transmitter current
selector.)
In general, use higher values with longer fiber optic cables.
The maximum setting is applicable to the maximum length of
the fiber optic link. See
Specifications of the fiber optic
master/follower link
(page 80).
Light intensity.
if using the
if using the
and
60.16 Force
and
60.16 Force
if using the
if using the master/follower
is set to
Parameters 395
Def/FbEq16
1
Not in use
0
1
2
3
4
5
6
Ring
0
1
10
RDCO