hit counter script

Table 15: Programming In Sigmaplan; Table 16: Operating Panel Display - Siemens SIGMASYS C Manual

Multifunctional danger control and indicating panels
Table of Contents

Advertisement

There are organisational and projected numbers for programming.
Organisational number:
Projected number:
The object number must have 3 digits and must be between 100 and 999. It is not possible to
assign a number twice (in SM88 and SIGMASYS). The projected number and the organisa-
tional number must be the same.
The organisational zone number must have 5 digits and is made up of the 3-digit object num-
ber and the 2-digit projected zone number.
The projected zone number must have 2 digits and must be between 01 and 99.
89 zones can be provided for each object.
Detector groups must always be entered with a projected number in the activation list for a
control module output (object/zone/detector group).
Example
Object org.
Object proj.
Zone org.
Zone proj.
Detector group org.
Detector group proj.
Control org.
Control proj.
Activation list MG 1

Table 15: Programming in SIGMAPLAN

Object org.
Zone org.
Activation via zone
Detector group org.
Control org.
Activation via

Table 16: Operating panel display

Multifunctional Danger Control and Indicating Panels SIGMASYS C and M (M-Modules)
Best.Nr. A24205-A337-B970 – Edition 12 (03/07)
displayed on the operating panel and on the printer.
required for internal processing and displayed on the printer.
Object
ZONE
101
101
101
11
101
11
101
11
Object
ZONE
101
101
11
101
11
101
11
Detector group
Detector
___ 1
0001
___ 1
0001
0001
Detector group
Detector
___ 1
___ 1
0001
5 Interfaces
at the
printer
at the
printer
29 / 128

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sigmasys m

Table of Contents

Save PDF