12 Monitored lines
not monitored for faults or tripping
MS8SE (control element) can be operated in operating mode 1 (permanent 1:1 assign-
ment) and inoperating mode 2 (system-wide control)
Only 3 parallel displays can be simultaneously activated on an MPL(reason: max. cur-
rent load of an MPL = 24 mA, 1 activated control unit requires approx. 4 mA,control
units and control elements are activated in the same cycle)
Fault detection
– all pulse-polling detector elements (including control elements) can cause a fault
Alarm buffering (ALZ) for Master20 and ABM
Event delay for BR800, BR81, BR82 and MS8EB
No fault delay
Detector zone formation
every detector in an MPL can be assigned one detector
cross-module formation not possible
Detector zone functions (as in SIGMASYS)
2-MG dependency
– 2-detector dependency
– ALORG (alarm organisation)
Alarm zone formation
cross-module formation possible
– mixing with MPC and GMG detector zones possible
Operating inputs (e.g. via receiver module MS8EB)
Maximal line data 300Ω, 250 nF
12.2.1
Differences vis-à-vis AMP (SM88) or PMG (BMS) Vis-à-vis AMP
no special AMP functions (suction systems, sterile areas)
no different sensitivities (+, –).
Pulse-polling
detector element
- BR800
- BR81
- BR82
FDOOT241-8
- BD857
- RSG8
- DR8
- DR8AU
- SDR8
-SDR8AU
- MS8EB
- ABM
80 / 128
Evaluation procedure ( code )
Standard
(0)
Standard
(0)
Standard
(9)
1blank value m
(0)
EMV
(9)
Standard
(0)
Standard
(5)
Standard
(5)
Standard
(5)
Standard
(1)
Standard
(5)
Standard
(1)
Standard
(3)
Standard
(B)
Remark
smoke detector
opt. smoke detector
opt. smoke detector
neural fire detector
heat detector
closed-circuit current alarm device
manual call point
manual call point with autom. inspection
manual call point
manual call point with autom. inspection
receiver module
addressing module