hit counter script

Current Requirement Calculation; Measuring The Battery Capacity; Table 26: Bridging Time - Siemens SIGMASYS C Manual

Multifunctional danger control and indicating panels
Table of Contents

Advertisement

I max =
Δu
=
χ
=
L
=
q
=
Cross sections over 2.5 mm
the SIGMASYS control and indicating panel.
11.5

Current requirement calculation

The maximum current requirement for the control and indicating panel is to be calculated us-
ing the form When calculating the alarm current, only the largest fire section should be taken
into account (largest current requirement of the system), i. e. when tripping the fire section
with the monitored alarm lines and the monitored control lines (max. value during simultane-
ous activation is decisive).
To calculate the power requirement for the Sinteso detector periphery you can also use the
Excel tables in the PSP (Product Support Platform).
11.6

Measuring the battery capacity

The size of the battery capacity is determined on the basis of the system's idle current and
the required bridging time. The battery bridging times are defined as follows in compliance
with VDE 0833 or VdS 2095:
Bridging time
If a standby power supply is available for the GMA and spare parts are provided and
mains supply failure is detected at any time (responsible service permanently busy)
and the maintenance technician is permanently available.
If the fault is detected at any time (responsible service permanently busy) and the
maintenance technician is available within 24 hours
If the conditions set for 4-hour and 30-hour operating time are not satisfied.

Table 26: Bridging time

On the basis of the control and indicating panel's and the external device's alarm current in
the event of an alarm. The alarm current for the alerting facility of the fire section with the
highest current requirements must be available for 0.5 hours (see VdS 2095).
The battery capacity (K) depends on the bridging time (tü) required and is calculated using
the following formula:
Bridging time t
Bridging time t
I
= idle current or recharging current
R
I
= alarm current
AL
The formulae are marked on the calculation form.
Multifunctional Danger Control and Indicating Panels SIGMASYS C and M (M-Modules)
Best.Nr. A24205-A337-B970 – Edition 12 (03/07)
maximum current in A
maximum permitted voltage drop of 0,5 V
special electric conductance for copper 58 m / mm
line length (forward and reverse line) in m
conductor cross section in mm
= 4 h
Ü
≥ 30 h
Ü
2
2
must be reduced with the help of series terminals in
https://psp.sbt.siemens.com
.
K = 1.56 * (t
·* I
Ü
R
K = 1.25 * (t
·* I
Ü
R
11 Power supply
2
VDE 0833 / VdS 2095
4 hours
30 hours.
72 hours.
+ 0.5 * I
) [Ah] and
AL
+ 0.5 * I
) [Ah]
AL
71 / 128

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sigmasys m

Table of Contents

Save PDF