Control facilities:
•
Control element
•
Switched cu
•
Output voltage:
•
Protection after transpon
•
Monitored control:
•
Resistivity:
With homopolar monitoring the internal resistance o
w
ithin a range of between 30 and 3300 ohms. (VdS monitored control line)
With reverse polar monitoring a blocking diode is required on each item of equipment with a
terminator resistance of 3k3 at the end of the cable.
The maximum control line resistance is 10% of the equipment resistance, up to a maximum of
150 ohms.
For further details see the "FDCIO223 Transponder Technical Documentation" EDMS Num-
ber 009122
8.2.4
Contact coupler SPF 5300
The contact coupler SPF 5300 is a multiple input module and is used for recording up to four
items of information or comm
with contacts, e.g. from announcement systems, sprinkler systems, technical alarms, techni-
cal faults, third-party systems, key-operated switches.
The contact coupler cannot be used for automatic detectors which are powered via
the primary line.
The a
dvantage of this element is that power is supplied to the element from the loop so t
n
o external PSU i
supply is not available for contacts with LED
Every input can be separately addressed, including as a detector zone.
UP to 128 contact coupler modules may be
coupler module occupies one address in the SIGMALOOP. Contact typ
be connected: Gold, Reed or equivalent.
Elements fed by the MPL may not be connected.
The inputs are to be programmed in strict c
Line connection
The contact coupler module can connect four lines.
The maximum length of all contact lines is 40 metres.
Multifunctional Danger Control and Indicating Panels SIGMASYS C and M (M-Modules)
Best.Nr. A24205-A337-B970 – Edition 12 (03/07)
rrent:
der:
ands via floating, monitored contacts. The inputs can be seized
s required. This can significantly reduce the cost of installation. Voltage
8 Transponders and loop elements
Relay
< 2 A
Input vo
ltage
2A M
- homopolar
30 Ω to 3k3
- reverse pola
3k3
- with feedback
see below
f the conne
connected to one SIGMALOOP. The contact
onsecutive order starting with input 1.
r
cted equipment is monitored
es of the contacts to
hat
47 / 128