Register No.
Function name
1058h
unused
1059h
Frequency source monitor
105Ah
Run command source monitor
105Bh to 108Dh unused
108Eh
Analog input O monitor
108Fh
Analog input OI monitor
1090h
unused
1091h
Pulse train input monitor
1092h to 10ADh unused
10AEh
PID deviation monitor
10AFh
10B0h to 10B1h unused
10B2h
PID output monitor
10B3h
10B4h to 1102h unused
*1
: Range modified from version 3.0
: Available from version 3.0
*2
Function
R/W
code
*2
d062
*2
d063
-
*2
d130
*2
d131
-
*2
d133
-
d153(HIGH)
*2
d153(LOW)
-
d155(HIGH)
*2
d155(LOW)
-
Monitoring and setting items
Inaccessible
0(Operator), 1-15(1-15 Multi-speed),
16(Jog frequency),
18(Modbus communication),
19(Option),
21(Potentiometer. available with
R
OPE-SR or OPE-SRmini),
22(Pulse train),
23(Calculate function output),
24(EzSQ),25([O] input),
26([OI] input), 27([O] + [OI] input)
1(Control terminal), 2(Operator),
R
3(Modbus network), 4(Option)
-
Inaccessible
R
0 to 1023
R
0 to 1023
-
Inaccessible
R
0 to 10000
-
Inaccessible
R
-999900
9 99900
~
R
-
Inaccessible
R
-999900
9 99900
~
R
-
Inaccessible
Ver.3− − − − 93
Data
resolution
-
-
-
1
1
-
0.01[%]
-
0.01[%]
-
0.01[%]
-