Hitachi WJ200-001S Instruction Manual page 67

Wj200 series single/three-phase inputs 200v/400v class
Hide thumbs Also See for WJ200-001S:
Table of Contents

Advertisement

218
Wire the Inverter Input to a Supply
Step 6: In this step, you will connect wiring to the input of the inverter. First, you must
6
determine whether the inverter model you have required three-phase power only, or
single-phase power only. All models have the same power connection terminals [R/L1],
[S/L2], and [T/L3]. So you must refer to the specifications label (on the side of the
inverter) for the acceptable power source types! For inverters that can accept
single-phase power and are connected that way, terminal [S/L2] will remain
unconnected.
Note the use of ring lug connectors for a secure connection.
Single-phase 200V 0.1 to 0.4kW
Three-phase 200V 0.1 to 0.75kW
Single-phase 200V 0.75 to 2.2kW
Three-phase 200V 1.5, 2.2kW
Three-phase 400V 0.4 to 3.0kW
L1
Power input
Chassis Ground (M4)
L1
Power input
Chassis Ground (M4)
Single-phase
RB
+1
+
-
N U/T1 V/T2 W/T3
Output to Motor
Single-phase
-
RB
+1
+
N U/T1 V/T2 W/T3
Output to Motor
Three-phase
RB
PD/+1
P/+ N/-
R/L1
S/L2 T/L3 U/T1 V/T2 W/T3
Power input
Output to Motor
Three-phase
RB
PD/+1
P/+ N/-
R/L1
S/L2 T/L3 U/T1 V/T2 W/T3
Power input
Output to Motor